CalQpro

Festival Lighting Power Load Calculator

Quick answer: Add fixtures with wattage, count, and connection type (120V or 208V). Get per-phase amps, neutral current, kW/kVA, and recommended breaker and generator size. Enter your on-site service β€” amps or kVA β€” for a go/no-go headroom check.

Calculate the total power draw of a festival lighting rig β€” fixture by fixture β€” with per-phase distribution, estimated neutral current (including the triplen-harmonic current non-linear LED loads push down the neutral even on a balanced rig), kW and kVA, a recommended generator size, and the required service size with the NEC 80% continuous-load rule applied. Handles both 120V line-to-neutral loads (standard lighting) and 208V line-to-line loads (chain motors, 208V video and distro). Enter the service you actually have on site β€” in amps or kVA β€” for a go/no-go headroom check. Built for tour managers, lighting designers, and festival production crews planning power distribution.

Advertisement

Last reviewed: April 2026Report an error

Fixtures & Loads

Default workflow: enter your fixtures and the calc auto-balances them across all 3 phases β€” what a competent distro tech does on-site. Toggle "Manual phase assignment" above only if you're spec'ing a fixed distro layout.

Quick:

Amps per leg from your tie-in spec β€” gives a go/no-go headroom check.

Drives the neutral-current estimate. LED switching supplies push 3rd-harmonic current down the neutral even when the legs are balanced.

Recommended Service Capacity

60 A

16.1 kW / 16.9 kVA on 208V 3-phase. Worst leg (L1): 47 A, 0.0% imbalance. Neutral β‰ˆ 28.2 A. Spec 60A service per leg + a 25 kVA generator (NEC 80% rule).

Per-Phase Breakdown (auto-balanced)

Imbalance: 0.0%

L1WORST

47 A

5,360 W

L2

47 A

5,360 W

L3

47 A

5,360 W

Worst-case sanity check (if everything lands on one leg)

Absolute maximum: 140.9 A on one leg β†’ would need 200 A service per leg (NEC 80% rule). For comparison, your auto-balanced spec is 60 A. If your distro layout is constrained or untested, plan toward the worst case.

Estimated Neutral Current

28.2 A

Imbalance portion: 0 A Β· Harmonic portion: 28.2 A

⚠ With an all-LED rig the neutral carries heavy 3rd-harmonic current β€” here it's about 60% of the worst hot leg even though the legs look balanced. Do not undersize the neutral conductor β€” size it at least equal to the phase conductors (NEC 220.61 treats the neutral as a current-carrying conductor on non-linear loads).

Real Power

16.1 kW

16,080 W

Apparent Power

16.9 kVA

load before margin

Generator Size

25 kVA

continuous-duty

Worst-Leg Amps

47 A

Service Capacity

60 A

Per-Phase Load Distribution

The L1 bar (highlighted) is the worst leg β€” service must be sized to this. Dashed red line shows your recommended service capacity after applying the NEC 80% rule.

Advertisement

The Formula

L-N amps = leg_watts / (V_LL/√3 Γ— PF) ; L-L amps = pair_watts / (V_LL Γ— PF) ; Leg total = |phasor sum of L-N + touching L-L| ; Service = worst_leg / 0.80 ; Generator = kVA / 0.80 ; Neutral = √(imbalanceΒ² + harmonicΒ²)
  • P_fixture = Watts per fixture (from spec sheet)
  • PF = Power factor (LED ~0.95, magnetic ballast ~0.85)
  • V_LL = Line-to-line service voltage (208 V for 3-phase festival service)
  • V_LL/√3 = Line-to-neutral voltage (per leg, ~120 V on 208V service)
  • 0.80 = NEC 80% continuous-load rule β€” applied to the breaker and the generator alike
  • kVA = Apparent power = real power (kW) Γ· power factor β€” what distros and gennies are rated in
  • L-L amps = 208V line-to-line load current β€” carried by BOTH legs of its pair (motors, 208V video/distro)
  • Leg total = Phasor (vector) sum of a leg's line-to-neutral and line-to-line currents at their voltage angles. Balanced delta β†’ √3 Β· I_pair, not 2 Β· I_pair.
  • imbalance = Fundamental neutral current from L-N loads: √(I₁²+Iβ‚‚Β²+I₃² βˆ’ I₁Iβ‚‚ βˆ’ Iβ‚‚I₃ βˆ’ I₃I₁)
  • harmonic = Triplen-harmonic neutral current from non-linear LED loads: k Γ— avg leg current (k β‰ˆ 0 linear, 0.25 mixed, 0.6 non-linear)

Source: NEC 2023 Article 210.20 β†—

How we verify our formulas β†’

How to Use This Festival Power Calculator

  1. 1Add each fixture: name, watts, count, connection type (120V line-to-neutral or 208V line-to-line), and phase assignment.
  2. 2Pick service voltage (208V 3-phase is standard for festivals).
  3. 3Set power factor (LED ~0.95, arc/discharge ~0.85).
  4. 4Optional: set fixture load type (all-LED rig = non-linear) and your available on-site service β€” in amps or kVA β€” for a headroom check.
  5. 5Read per-phase amps, neutral current, kW/kVA, recommended service size, and generator size.

Frequently Asked Questions

Advertisement

</> Embed this calculator on your website
<iframe src="https://calqpro.com/calculators/festival-power-load-calculator" width="100%" height="600" frameborder="0" title="CalQpro Calculator" loading="lazy"></iframe>
<p>Powered by <a href="https://calqpro.com">CalQpro</a></p>

Advertisement